  • Power Master Technology Co., Ltd.

    Inverter UPS AVR Charger, DC to DC, DC To AC Power Inverter, UPS, SMR.

    Products

    Online UPS Systems

    ups systems

    • Model No: PM-90120CP
    • Factory Location: Taiwan
    • Sample Request: No
    • Target Markets: Worldwide

    Detail Information

    Description :

    1. Character:
    -Advanced technology of PWM, DSP and IGBT switching components Designed to use a high frequency, highly efficiency DSP/IGBT and PWM technology in converting DC to AC power.
    -True Galvanic isolation design Solve ultimately the problem of power system, including noise, lightning, and leakage current etc.
    -Multi-CPU design and software/hardware cooperate control Make the system extremely high reliable.
    -Plug & Play modular design To allow for each power circuit to be easily removed for quick maintenance and troubleshooting.
    -Each phase with individual inverter supporting Characteristics will not be violated under 100% unbalance load.
    -Protection against detaching and floating of the neutral of input power supply Ensure the safety and stability of the UPS power output.
    -Protection from user error Advanced circuitry prohibits damage to the system when the user makes an operational mistake.
    -Intelligent charger with temperature compensation (option) Prolong the battery life expectancy. And with huge charging power (selectable), can charge very big capacity, long back-up time battery bank.
    -Intelligent, safe battery test circuitry Test the battery without the risk of output AC failure in case of battery bad. And with battery fluid leakage and improper grounding detect circuitry, can ensure safety of the battery bank.
    -Intelligent fan speed control Increase the fan life expectancy and reduce audible noise.
    -Reasonable heat evacuation passage design Main PCBs are designed in a holder to separate the control circuitry and power circuitry. Therefore, the UPS system can operate under harsh environment.
    -Cool start function Can be started without AC mains (with battery only) and protected from high inrush current.
    -Variety of accessory (options) Remote control panel, 3 phases software for PC monitoring, auto dialing module, battery monitoring module, 3 phases SNMP card, and emergency power-off switch are available.
    -Microprocessor design base
    -Mini- remote control panel (option)
    -Multiple output sockets
    -Minimum foot print area design, light weight
    -Built-In AVR for wider input range
    -Auto re-charging whenever AC exist.
    -Hot swappable battery by users
    -RS232 communication port
    -Tel/modem internet surge suppression
    -DC Start function
    -Green power function
    -Auto detecting frequency 12-Pulse Full Controlled Rectifier (option) To reduce total harmonic current and for UPS.

    2. Description:
    3 phase in 3 phase out online UPS.
    Intelligent, digitalized, and true galvanic isolation online design for Power Plants.

    Specification :

    MODELPM-90120CP
    CAPACITYCapacity120KVA / 96KW
    INPUT (RECTIFIER)Input Voltage220 / 380 / 460, 208/ 380, 400, 415
    Input Range±20% ( > ±20% is available upon request)
    Input Frequency50 / 60 Hz ± 5Hz
    Power Walk In0% - 100% : 20 sec
    Efficiency 98%
    Voltage Regulation±1%
    BATTERYBattery Type / PcsMaintenance free lead-acid batteries / 12V x 29pcs
    Maximum Charge
    Current Adc (Selectable)
    60
    Battery StartYes, UPS can be started without AC source.
    INVERTEROutput Voltage220 / 380 / 460, 208 / 380, 400, 415  ± 1 %
    Wave FormSine Wave
    Output Power Factor0.8
    Frequency Lock Range50 / 60 Hz ± 3Hz
    Output Frequency
    (Free Running)
    50 / 60 Hz ± 0.1 Hz
    Phase Shift Under 100% Unbalance Load< 0.5
    THD (Linear Load)< 2 %
    Overload <110%Continuous
    Overload 110-125%15 minutes
    Overload 125-150%10 minutes
    Overload >150%1 minute
    Efficiency (100% Load)95%
    STATIC SWITCHVoltage Range173-277 VAC (L-N)
    Mains ¡÷ Inverter 
    Inverter ¡÷ Mains
    0 ms
    OVERALL CHARACTERISTICSOverall Efficiency93%
    Maximum Heat 
    Dissipation (Kw)
    6.5
    Height x Width x Depth (mm)1600 x 550 x 800
    Weight 
    (Kg, without battery)
    1180
    Audible Noise< 67 dBA (At 1 M)
    Temperature0-40(32-104)
    Humidity0% - 90% (Non-Condensing)
    Altitude 
    EN50091-1,-2YES
    Short Circuit ProtectionYES
    Lightning / EMC FilterMOV / Input&Output (FCC CLASS A)
    Galvanic IsolationInput&Output true Galvanic isolation
    LED, LCD, BuzzerYES
    Remote Control / 
    Communication Interface
    Monitoring 1~99 UPS simultaneously / Dry contact, RS232, RS485

    Power Master Technology Co., Ltd.

    • Taiwan
    主站蜘蛛池模板: japanese日本护士xxxx18一19 | 女人让男人直接桶| 国产乱码精品一区三上| 久久婷婷激情综合色综合俺也去 | 男女特黄一级全版视频| 成人午夜性影院视频| 向日葵app下载网址进入在线看免费网址大全| 久久亚洲sm情趣捆绑调教| 香蕉人人超人人超碰超国产| 日韩免费a级在线观看| 国产成人A亚洲精V品无码| 久久综合亚洲鲁鲁五月天| 麻豆一区二区三区蜜桃免费| 日韩免费观看一级毛片看看| 国产在线高清精品二区色五郎| 久久天天躁日日躁狠狠躁| 野外做受又硬又粗又大视频| 无翼乌r18无遮掩全彩肉本子| 国产va在线视频观看| 中文字幕66页| 男女边吃奶边做边爱视频| 大乳女人做受视频免费观看| 亚洲白色白色永久观看| 1000又爽又黄禁片在线久| 校霸把学霸往死里做| 国产又猛又黄又爽| 中文字幕无码乱码人妻系列蜜桃 | 漂亮女教师被浣肠| 国产精品自在欧美一区| 亚洲www在线| 高分少女免费观看第一季| 无码精品久久久久久人妻中字| 向日葵app下载观看免费| chinese乱子伦xxxx视频播放 | 2022国产麻豆剧果冻传媒剧情 | 欧洲精品久久久AV无码电影| 国产小视频在线免费| 中文字幕无码精品三级在线电影| 精品国产一区二区三区免费| 埋在老师腿间喝圣水| 亚洲一成人毛片|